| Brand Name: | SKYLINE |
| Model Number: | SL-FL13 |
| MOQ: | 1 |
| Price: | Negociate |
| Supply Ability: | 1 Set/Month |
The Single Burning Item (SBI) test determines the reaction-to-fire behavior of building products (excluding floorings) when exposed to the thermal attack of a single burning item — a sand-box burner supplied with propane. Heat and smoke release rates are monitored instrumentally and visually to classify products under EN 13501-1.
Two vertical specimens form an inside corner, and a propane sand-box burner (typically 30 kW for the first 300 s, then 20 kW) is placed at the corner. The specimen's lateral flame spread, heat release and smoke production are measured by oxygen consumption and light obscuration in the exhaust. The resulting outputs — FIGRA, SMOGRA, THR and LFS — drive the Euroclass (B, C, D) classification.
| System Composition | Combustion laboratory, control room, 2 small carts, exhaust pipe, fixed frame, flue gas collection system, integrated measurement system device, data collection and analysis device, and gas supply control device. |
|---|---|
| Combustion Chamber Dimensions | Length (3.0 ± 0.2) m × width (3.0 ± 0.2) m × height (2.4 ± 0.1) m. |
| Chamber Construction | Standard combustion chamber composed of stainless steel plate and calcium silicate board A1 plate; the test furnace is installed on site. |
| Exhaust & Sampling | A collecting hood at the top of the room connects to a smoke pipe leading to the sampling piping. Combustion heat release and combustion products from the sample are discharged through the exhaust pipe during the test. |
| Access & Observation | An opening in the combustion chamber wall allows easy entry of the small cart, with natural air flow beneath the trolley. Observation windows are provided on both sides of the front surface of the vertical test plates. |
| Ignition Source | 31 kW propane right-angle sand-box burner (side length 250 mm, height 80 mm) placed at the vertical corner of the trolley. |
| Airflow Distribution | The cart is positioned so that its rear opening aligns with the openings in the combustion chamber wall. A perforated plate (8 mm diameter holes, 60% open area) at the air inlet at the bottom of the trolley distributes airflow evenly along the combustion chamber floor. |
| Specimen Fixture | Adjustable governance fixture for convenient loading and unloading of samples. |
| Sandbox Burner Configuration | One burner on the floor of the trolley (main burner) and one fixed on the frame column; propane gas passes through the sand-box burner to produce a heat output of 30.7 ± 2.0 kW. |
SBI classifies non-flooring building products into Euroclasses B, C and D (and s1/s2/s3 smoke classes) under EN 13501-1.
A propane sand-box burner provides 30 kW for the first 300 s, then 20 kW, simulating a single burning item attacking the corner of two specimens.
FIGRA (fire growth rate), SMOGRA (smoke growth), THR and lateral flame spread (LFS) are the key indices for classification.
No — SBI excludes floorings; flooring uses the radiant panel (ISO 9239-1) instead.