    Product Details:

    Place of Origin: China
    Brand Name: SKYLINE
    Certification: CE
    Model Number: SL-7603B

    Payment & Shipping Terms:

    Minimum Order Quantity: 1 unit
    Price: negotiated
    Packaging Details: plywood case
    Delivery Time: 10 work days
    Payment Terms: T/T, L/C, Western Union, MoneyGram
    Supply Ability: 1 unit/ month
    Contact Now
    Detailed Product Description
    Standards: IEC60332-2-1:2004 Vertical Burning Chamber: W300xH1200xD450mm
    Length Of Specimen: 600±25mm Gas Flow Range: 0.1-1L/min
    Area Flow Range: 0.1-1m3/h SKYLINE: Single Insulated Wire And Cable Vertical Flame Test Equipment

    Single Insulated Wire and Cable Vertical Flame Test Equipment , Specimen Length 600 ± 25mm

     
    Application
    Applies to check thesingle insulation wire and cable vertical spreading test which total section area less than 0.5mm2.
     
    Standards
    According to  IEC60332-1-1:2004,  IEC60332-1-2:2004,  IEC60332-1-3:2004, EN50265-1, EN50265-2-1.
     
    Main parameters
     Vertical burning chamber  W300xH1200xD450mm
     Gas  Use high purity propane gas or liquefied petroleum gas (provide by user-self)
     Specimen length  600±25mm
     Area of specimen  Total section area less than 0.5mm2
     Testing temperature  This device is located in a stuffiness room and the temperature keeping the 23±10℃ for testing
     Burning time  continuously setting between 0.1-999.9S, during the setting time flame could continuously burning the specimen
     Control function  Switch can choose to be manual or automatically according to the actual needed
     Gas flow range  0.1-1L/min
     Area flow range  0.1-1m3/h
     Burner  500W for standards power, 125±25mm for total height of the flame

     