Send Message
SKYLINE INSTRUMENTS CO.,LTD

        Skyline Instruments Co.,LTD

 

                   We only manufacture Lab Testing Equipment

Home
Products
VR Show
About Us
Factory Tour
Quality Control
Contact Us
Request A Quote
Home ProductsFire Testing Equipment

IEC60695-11-03 Fire Testing Equipment Single Cable Vertical Flammability Tester

IEC60695-11-03 Fire Testing Equipment Single Cable Vertical Flammability Tester

  • IEC60695-11-03 Fire Testing Equipment Single Cable Vertical Flammability Tester
IEC60695-11-03 Fire Testing Equipment Single Cable Vertical Flammability Tester
Product Details:
Place of Origin: China
Brand Name: SKYLINE
Certification: CE
Model Number: SL-7603C
Payment & Shipping Terms:
Minimum Order Quantity: 1 unit
Price: negotiated
Packaging Details: Plywood case
Delivery Time: 10 working days
Payment Terms: T/T, L/C, Western Union, MoneyGram
Supply Ability: 1 unit/ month
Contact Now
Detailed Product Description
Standards: IEC60332-1-1:2004 Vertical Burning Chamber: W300xH1200xD450mm
Length Of Specimen: 600±25mm Gas Flow Range: 0.1-1L/min
High Light:

flammability test apparatus

,

flammability testing labs

IEC60695-11-03 Single Cable Vertical Flammability Tester 
 

Product introduction

Single Cable Combustion Tester is the most widely used and lower cost of cable fire performance test equipment, which can meet the standards IEC 60332-1-1:2004 in the provisions of technical indicators and requirements. Single cable combustion Tester is used to test the flame retardant property of the cable's insulating layer under abnormal conditions such as overheat and overcurrent. It can be used in vertical cable or fiber flame spread test, also can be test the state of flaming droplets during combustion.

 
Application
Applies to check thesingle insulation wire and cable vertical spreading test which total section area less than 0.5mm2
 
Standards
According to IEC60332-1-1:2004, IEC60332-1-2:2004,  IEC60332-1-3:2004, EN50265-1, EN50265-2-1
 
Main parameters
 Vertical burning chamber  W300xH1200xD450mm
 Gas  Use high purity propane gas or liquefied petroleum gas (provide by user-self)
 Specimen length  600±25mm
 Area of specimen  Total section area less than 0.5mm2
 Testing temperature  This device is located in a stuffiness room and the temperature keeping the 23±10℃ for testing
 Burning time  continuously setting between 0.1-999.9S, during the setting time flame could continuously burning the specimen
 Control function  Switch can choose to be manual or automatically according to the actual needed
 Gas flow range  0.1-1L/min
 Area flow range  0.1-1m3/h
 Burner  500W for standards power, 125±25mm for total height of the flame
 Temperature measurement system  according to GB/T5169.14-2007 and IEC60695-11-03 standard requirements, including temperature copper (10g), K type thermocouple and diameter is 0.5 mm with stainless steel sheathed, stopwatch and thermometer etc.

 

Automotive Single Wire.pdf

IEC60695-11-03 Fire Testing Equipment Single Cable Vertical Flammability Tester 0
What is a Vertical flame Test?
A test specimen is positioned vertically above a controlled flame and exposed for a specified period of time. Following exposure, the flame source is removed. Measurements are made on the length of time that the specimen continues to flame and the time afterglow continues after the flame source has been removed.
What is the flame exposure test for a cable?
Table 1: UL Control and Instrumentation Cable Standards Containing Vertical Flame Tests The UL Flame Exposure test of UL 1685 measures the flame spread in groups of cables in a steel ladder tray. The tray is 12 inches wide, 3 inches deep and 96 inches long.
 

Contact Details
SKYLINE INSTRUMENTS CO.,LTD

Contact Person: Charlie

Tel: 13310806019

Fax: 86-769-38818154

Send your inquiry directly to us (0 / 3000)

Other Products